TM 55-1520-240-23-6
7-100
ADJUST INTEGRATED LOWER CONTROL ACTUATOR (ILCA) CROSS FEEDBACK
TRANSDUCER (AVIM) (Continued)
7-100
10.
Set SYSTEM SELECT switch (21) to SAS 2.
11.
Check DVM (31) indication. Reading shall not
exceed 0.043.
NOTE
If DVM (31) reading is greater than
0.043, replace tranducer, repeat Task
7-100.
12.
Lockwire nut (25) to bearing (26). Use lockwire
(E230).
INSPECT
Change 1
7-479