TM 55-1520-240-23-6
7-97
EXTENSIBLE LINK ACTUATOR CYLINDER FUNCTIONAL TEST (AVIM)
(Continued)
7-97
TEST 1
TRANSDUCER NULL TEST
36.
Perform steps 1 thru 35. Check initial control and
valve settings in steps 20 and 21.
37.
Set LINK TEST switch (29) to SELF FDBK.
38.
Read DVM (55). Reading shall be 0.018 or less.
Record reading. If reading is more than 0.0180,
adjust transducer (Task 7-101).
39.
Set LINK TEST switch (29) to VALVE.
40.
If no further testing is required, perform normal
shutdown (TM 55-4920-428-13).
END OF TRANSDUCER NULL TEST
7-384