TM  55-1520-240-23-9 11-277 BENCH TEST AFCS  COMPUTER  (AVIM) (Continued) 11-277 307. Set ANALOG  SIGNALS AIRSPEED  switch  (35) to  6.  Read  and  record  V22  AC/DC VOLTMETER (10) reading. 308. Calculate  V23.  Subtract reading  of  step  293  from reading  of  step  307  (V23  =  V22  -  V19).   Result shall  be  -3.20 to  -4.10  volts. 309. Set ANALOG  SIGNALS AIRSPEED  switch  (35) to  5. 310. Set METER  switch  (6) to  AC. 311. Set CIRCUIT  SELECT  TENS  switch  (8) to  20. 312. Set CIRCUIT  SELECT B  UNITS  switch  (11)  to  6. 313. Set CIRCUIT  SELECT  A/B  SELECT  switch  (9) to  B. 314. Adjust ANALOG  SIGNALS  PITCH  ATT  HSI  HDG pot.  (42) toward  900  until  AC/DC  VOLTMETER reads  +8.88. 315. Set METER  switch  (6) to  DC. 316. Set CIRCUIT  SELECT  TENS  switch  (8) to  10. 317. Set CIRCUIT  SELECT A  UNITS  switch  (18)  to  4. 318. Set CIRCUIT  SELECT  A/B  SELECT  switch  (9) to  A. 319. Set METER  RANGE  switch  (7) to  2V. 320. Adjust  ANALOG  CIRCUITS  ATT  synchro  (38) toward  170  until  AC/DC  VOLTMETER (10) reads 0  or obtain  a  NULL.  Read  ATT  synchro  dial setting.  Reading  shall be  170.2º  to  172.7º. 11-1099